Cover story, continued...
User Restrictions and Controller protections: Part Two
Last month we focussed on some of our control features designed to prevent tampering and
to protect your equipment. Temperature Setpoints, Control Mode, Keypad Locks and Ramp Restrictions were
highlighted in round One. In round Two of our Cover Story, we continue our tutorial.
Unoccupied & Night Setback Mode
When the building is no longer occupied, night setback & unoccupied options are available.
These options reduce energy consumption and will prolong equipment life cycle. There are two options;
Night setback (NSB) or Unoccupied (NoOcc). The two modes are identical except for the terms used.
Unoccupied heating & cooling setpoints speak for themselves. The setpoints are adjustable and the range
large enough to prevent heat or cool to be activated while unoccupied.
The override delay function is to allow users to bring the unit back to occupied mode for the duration
of the parameter.
Motor mode is only available on the VAV box controller and dictates the damper
position when unoccupied.
For fan coil controllers, the two configurations that will dictate the
operation of the unit when unoccupied are the mode & fan mode. The mode can be set to maintain unoccupied
setpoints or can be set to "off" to prevent unit from running while unoccupied. Note that there is a safety
(freeze protection) in case the temperature drops below 4˚C (39˚F) that will restart the unit in heating to
prevent the zone from freezing. This will work even if the unit is configured to “off” while unoccupied.
The fan mode can be set to automatic and will follow demand. If there are no demands, the fan will be off.
The fan mode also be configured at a certain speed (low, medium or high) if continuous fan operation is required for ventilation purposes.
|
EVCB |
EFCB |
TUCB/TUHB |
NSB/NoOcc setpoint Cool |
AV.18 |
AV.12 |
AV.12 |
NSB/NoOcc setpoint Heat |
AV.19 |
AV.13 |
AV.13 |
NSB override delay |
AV.60 |
AV.85 |
AV.85 |
NoOcc override delay |
AV.61 |
AV.86 |
AV.86 |
NSB/NoOcc mode |
BV.20 |
BV.35 |
BV.35 |
NSB/NoOcc motor mode |
MSV.36 |
Not available |
Not available |
NSB/NoOcc fan mode |
Not available |
Not available |
MSV.26 |
Humidity Control (EFCB & TUCB/TUHB only)
For occupied mode, only one setpoint is used. The controller will decide if humidification or dehumidification is
required based on the present relative humidity reading, the proportional & dead band. The EFCB and TUHB can use the
internal or external humidity sensor using the configuration humidity control source. The setpoint can be limited by
using minimum & maximum humidity setpoints or can be locked by using humidity setpoint lock.
The humidity control mode enables the unit to operate in automatic (humidify & dehumidify), humidification only, dehumidification only or "off".
|
EFCB |
TUCB/TUHB |
Humidity Setpoint (occupied) |
AV.73 |
AV.73 |
Humidity minimum setpoint |
AV.74 |
AV.74 |
Humidity maximum setpoint |
AV.75 |
AV.75 |
Dehumidification unoccupied setpoint |
AV.76 |
AV.76 |
Humidify unoccupied setpoint |
AV.77 |
AV.77 |
Humidity control source |
BV.25 |
BV.25 (TUHB only) |
Humidity setpoint lock |
BV.26 |
BV.26 |
Humidify ramp lock |
BV.27 |
BV.27 |
Dehumidify ramp lock |
BV.28 |
BV.28 |
Humidity control mode |
MSV.5 |
MSV.5 |
If the unit is configured to hold setpoints while in unoccupied mode (see unoccupied & night setback section),
two unoccupied setpoints are available: one for humidification and one for dehumidification. Most of the time, humidification
will not operate while in unoccupied mode. The unoccupied humidify setpoint range is large enough to prevent the humidifier
from operating in that mode. For dehumidification, the relative humidity should never go over 60%RH to prevent bacterial
growth and mildew. When using a BMS, ramps can be locked out by using humidify & dehumidify ramp lock functions.
Next month:
n our third and final round, we will complete the series with a tutorial on
flow switches, controller display information and additional safeties. Stay tuned!